NYC 9/11 Public Portal Document
Data File : C:\MSDCHEM\1\5973N\02MAR01\03245.D Vial: 6
♦ Acq On : 1 Mar 2002 2:28 pm Operator:
Sample : 508 scan Inst : Instrumen
Mise : March 1, 2002 Multiplr: 1.00
MS Integration Params: SPLIT.P
Quant Time: Mar 04 10:50:48 2002 Quant Results File: HP022102.RES
Quant Method : C:\MSDCHEM\l..-\HP022102.M (RTE Integrator)
Title : 508 scan method
Last Update : Mon Feb 25 10:47:59 2002
Response via : Initial Calibration
DataAcq Meth : HP020702
Internal Standards R.T. Qlon Response Cone Units Dev(Min)
1) 1,4-Dichlorobenzene-d4 9.71 152 1587119 20.00 ug/L 0.00
10) Naphthalene-d8 13.20 136 6878638 20.00 ug/L 0.00
17) Acenaphthene-diO 18.33 164 3418501. 20.00 ug/L 0.00
29) Phenanthrene-diO 22.63 188 5582169 20.00 ug/L -0.01
38) Chrysene-dl2 30.49 240 4417674 20.00 ug/L -0.03
44) Perylene-dl2 34.41 264 2895941 20.00 ug/L -0.04
System Monitoring Compounds
37) 2,4-DDD 27.72 235 429121 5.77 ug/L 0.00
Spiked Amount 5.000 Recovery = 115.40%
Target Compounds Qvalue
20) Dimethylphthalate 18.34 163 548244 2.64 ug/L # 57
21) 2,6-Dinitrotoluene 18.33 165 431368 9.01 ug/L # 27
(#) = qualifier out of range (m) = manual integration
03245.D HP022102.M Mon Mar 04 10:50:49 2002 Page 1
NYC-WTC_000006087