133-135 Greenwich Slreet/21-23 Thames Street
Airtek Project 05-0701 - November 4, 2005
• The XAD-2 resin is dried in a fume hood for 16 hours instead of dried in a
vacuum oven with ultra-pure nitrogen for 2-4 hours.
• The laboratory uses methylene chloride-rinsed aluminum foil instead of hexane-
rinsed aluminum foil.
• The laboratory uses methylene chloride for the extraction solvent instead of
10% ether/hexane and therefore does not perform the precleaning extraction of
800 mL methylene chloride of the Soxhlet apparatus.
• The final extract is brought down to a volume of 0.5 mL in methylene chloride.
11.1.2.2 Dioxin Extraction by EPA Method T0-9A
• The laboratory uses toluene for the extraction solvent instead of 10% diethyl
ether/hexane.