Ambient air monitoring program, 130 Liberty Street

Machine-extracted title · confidence 54%

Ambient air program report for 130 Liberty Street deconstruction August 2005.

NYC-WTC_000438517–000438547
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

5.1 PM10/PM2.5 Monitoring (“Real-Time’VContinuous)

5.1.1 Beta - Attenuation PMjoand PM2.5 Monitors (All Sites)

The monitors selected to continuously measure PMio and PM2.5 are beta-attenuation monitors manufactured by Met One Instruments, Inc. (Met One). The Met One E-BAM will be used for continuous PMio and PM2.5 measurements. The instrument operates on the principle of beta attenuation.

The E-BAM has not been officially designated by USEPA as either Reference or Equivalent Method. However, the E-BAM design is descended directly from the BAM-1020 (which has received USEPA’s designation as an Automated Equivalent Method - EQPM-0798-100), modified to provide portable batteiy operation and produce measurements in real-time (averaging times less than 1 hour). The accuracy and precision of the E-BAM are consistent with USEPA requirements for Class III designation for PMio. Class III equivalent method instruments include any candidate instruments that cannot qualify as Class I or Class II instruments. These may either be filter-based integrated samples not meeting Class I or Class II criteria, or filter or non-filter based continuous or semi-continuous samplers. Other methods include all non-FRM or non-equivalent measurement methods capable of characterizing fine particles that may not be or have not yet been classified as an equivalent method. Existing manual and continuous analyzers in this category include the dichotomous sampler, IMPROVE samplers, nephelomethers, beta attenuation monitors, and Tapered Element Oscillating Microbalances (TEOMs). Such instruments are not precluded from becoming equivalent on a site-specific, regional or national basis.

The beta attenuation process uses a small source of beta particles (carbon-14, 60 microcuries) is coupled to a sensitive detector that counts the emitted beta particles. The dust particles are collected on a filter tape that is placed between the beta source and the detector. Dust on the filter will intercept some of the beta particles. The reduction of beta particles is proportional to the amount of dust on the filter, which allows the mass of dust to be determined from the beta particle counts. The dust mass is combined with the air volume collected during the filter exposure time to determine the PM concentration.

The E-BAM monitors will be equipped with particle size selective inlets. The design of the inlets is such that particles larger than the desired size range will be removed from the air flow, based on the air flow rate. The units will be equipped with an inlet head to separate PMio or PM2.5. Sampling flow rate is critical to maintain the proper particle size cut points of the inlets. Flow rates are maintained at 16.7 liters per minute (LPM) in the E-BAM monitors using an integral flow meter, pressure sensor, and ambient temperature sensor on board each monitor.

The data from the E-BAM units will be recorded by digital data loggers using the analog signal outputs of the monitors. The PM|o and PM2.5 data from the E-BAM monitors will be recorded as 10-minute, and daily (e.g., 8 AM - 8 AM) averages.

L2005-149 (081205)v2 5-2 5023623.2

CITY_21MC100_003243389

NYC-WTC_000438531

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000438531Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000427190

Chain-of-custody for August 2005 ambient air monitoring at 130 Liberty Street deconstruction site, LMDC.

Similar indexed content

Compare copies and versions →