NYC 9/11 Public Portal Document
FROM:
George - Taylor Env.
TO:
LEMPERT, ALEX
DATE:
08/13/2002 03:19:14 PM
SUBJECT:
Stuyvesant HS Elevator Shaft cleaning and testing protoc
ol Rev.#l
Alex
Elevator Shaft(s) Cleaning and Testing Protocol
1. Prior to any cleaning work being performed inside the elevator
shaft, each set of elevator doors on every floor ( not being used to
access the elevator car and/or shaft ) shall be sealed with a loose
diaphragm consisting of two layers of six-mil plastic sheeting sealed
with tape.
2. A licensed elevator mechanic shall secure the elevator car at the
highest elevation of the elevator shaft. The HVAC cleaning contractor
shall clean the elevator pit area using wet methods and/or HEPA
vacuum.
3. Under the supervision of a licensed elevator mechanic, the HVAC
cleaning contractor shall clean all accessible interior surfaces of
the elevator shaft and accessible exterior surfaces of the elevator
car using wet methods and/or HEPA vacuum.
4. A visual inspection of all cleaned surfaces will be conducted to
ensure they no visible dust/debris remain.
5. At the conclusion of a successful visual inspection , all
accessible interior surfaces of the elevator shaft will be sealed
with a clear-coat encapsulant.
6. The ceiling access hatch of the elevator car will be opened , and
the car will ascend and descend the shaft a number of times.Two air
samples will then be collected inside the elevator car to be analyzed
for asbestos (TEM AHERA) and airborne lead (NIOSH 7082).
CITY_21MC100_013074218
NYC-WTC_000433857
OCR can misread numbers and units. Confirm readings against the page image before using them.