Mr. Bernard P. Orlan February 7, 2002 Indoor Air Quality Assessment Page 3 RSMSOM ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 11:00 A.M. and concluded at approximately 3:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 72.7°F to 77.6°F. Twelve (12) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 40.1 to 43.5°F.
Relative Humidity
The relative humidity indoors ranged from 15.7 to 20.4 percent. All of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 14.1 to 30.5 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 546 ppm to 1101 ppm. All of the CO2 measurements was below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. Tire maximum outdoor (background) CO2 concentration was 509 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1209 ppm (background level -t- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppms for the interior readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0-1 ppm for all collected readings.
Respirable Particulates (PM2_j)
Respirable particulate concentrations* indoors ranged between 16 pg/m^ to 37 pg/m^. None of the measurements were above the NPAAQS of 65 ug/nP 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 26 pg/m^. The PM2.5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration measurements ranged from 30 to 42 pg/m^ with an average of 37 pg/m^.
CONFIDENTIAL, CITY_21MC100_003386082 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000410429
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000300655
ATC IAQ field report for PS 150M, Feb 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300651
ATC indoor air quality evaluation at PS 150M for re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375473
Indoor air quality measurements collected Feb 7, 2002 for PS 150M.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300642
ATC IAQ measurements for PS 150M prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375465
Indoor air quality measurements for P.S. 150M requested by BOE.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410567
IAQ measurements report for PS 150M prior to re-occupancy, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410451
IAQ measurements at PS 150M; BOE pre-occupancy evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410435
IAQ measurements report for PS 150M requested by NYC BOE.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178010
Letter reporting indoor air quality measurements collected at P.S. 150M on June 26, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289350
Indoor air quality measurements collected for PS 150M; BOE-ordered.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249700
IAQ measurements at PS 150M before re-occupancy; scope described.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410543
IAQ measurements conducted for BOE pre-occupancy at PS 150M.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000300743
ATC provides IAQ evaluation for PS 150M in Mar 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300779
ATC IAQ measurements at PS 150M for BOE, March 11, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410435
IAQ measurements report for PS 150M requested by NYC BOE.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249784
ATC IAQ measurements report for PS 150M, April 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249832
IAQ measurements for PS 150M to evaluate pre-occupancy conditions.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410567
IAQ measurements report for PS 150M prior to re-occupancy, March 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000300655
ATC IAQ field report for PS 150M, Feb 2002.
Similar indexed content
NYC-WTC_000300651
ATC indoor air quality evaluation at PS 150M for re-occupancy.
Similar indexed content
Indoor air quality measurements collected Feb 7, 2002 for PS 150M.
Similar indexed content
NYC-WTC_000300642
ATC IAQ measurements for PS 150M prior to re-occupancy.
Similar indexed content
Indoor air quality measurements for P.S. 150M requested by BOE.
Similar indexed content