Indoor air quality report, PS 234M

Machine-extracted title · confidence 35%

IAQ measurements report for PS 234M dated Jan 30-31, 2002.

NYC-WTC_000410283–000410286
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan January 30, 2002 Indoor Air Quality Assessment Page 4 P. S. 234M ATC Project No. 15-19125-0279

concentration was below the USEPA recommended concentration for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentration ranged from 13 to 69 pg/m^ with an average of 40 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TYOCConcenp^aiim

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Measurements of CO2, CO and TVOCs were within applicable standards and guidelines. All of the relative humidity measurements were also within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 2. Five (5) temperature measurements were below the range of 68 to 75O F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 Two (2) of the measurements were above the recommended range. 3. One (1) measurement of respirable particulates was higher than the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 261 or 212.

Sincerely, U TC ASSOCIA TES INC. Reviewed by:

Yiannis Efstath; James R. Cohn, CIH. CSP Project Manager Regional Manager Industrial Hygiene Division

Attachment

CONFIDENTIAL, C:iTY_21MC100_001897954 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008 NYC-WTC_000410286

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000410286Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →