Mr. Bernard P. Orlan January 29, 2002
Indoor Air Quality Assessment Page 4
P. S. 234M ATC Project No. 15-19125-0279
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC .
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The building was occupied at the time of the assessment;
• No-smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Measurements of CO2, CO and TVOCs were within applicable standards and guidelines;
2. Thirty-six (36) temperature measurements were below the range of 68 to 750 p (at 50
percent relative humidity) recommended by ASHRAE Standard 55-1992;
3. Twelve (12) indoor measurements of relative humidity were below the ASHRAE
recommended range of 30 to 60 percent for occupant comfort.
4. Three (3) measurements of respirable particulates were higher than the NPAAQS of 65
p.g/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
261 or 212.
Sincerely,
J TC ASSOCL4 TES INC.
Reviewed by:
/
Yiannis Efstathiou James R. Cohn, CIH, CSP
Project Manager Regional Manager
Industrial Hygiene Division
Attachment
CONFIDENTIAL, CITY_21MC100_001897935
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000410272
OCR can misread numbers and units. Confirm readings against the page image before using them.