NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 5 pages

Asbestos building assessment chain of custody, Building #100

Machine-extracted title · confidence 54%

Chain-of-custody for visual, bulk, and air asbestos sampling at Building 100, dates in 2001.

NYC-WTC_000409106–000409110
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

4.2 Air Sampling Procedures

ALC’s licensed technicians collected air samples using TEM Methodology. The technician collected five (5) air samples on each floor. The samples were taken in three (3) apartments and at two separate areas m the hallways on each floor. The technician identified the locations that appeared to contain the most visible dust and debris to perform sampling.

The air samples were collected using high volume air sampling pumps. Once the pumps were in place the air sampling technician recorded the location, time, date, sample numbers, pump number, flow rate, start and stop times and his imtials.

The air cassette was independent of the pump motor. This is to prevent the vibrations of the motor from affecting the fibers in the cassette. A separate stand or tripod was used to hold the cassette in place. The cassette was angled 45 degrees downward from the horizontal stand. This is to insure that no asbestos will drop mto the cassette while sampling.

Using a rotameter, we calibrated each pump to the required flow rate, noting this rate on tiie sample record. After calibrating the pumps, the end cap from the cassette was removed; the pump was turned on and run for the required amount of time.

The sampling pumps were checked periodically to ensure they were still operating, the cassettes were still in place, and no one has disturbed the equipment. If at any time the area being sampled was suspected of having high fiber counts, the filter inside the cassettes were examined for “overloading”, or an excessive amount of fibers and/or debris on the filter.

When the pre-determined volume of air has been collected, the technician then calibrated the sampling pump again to determine the current flow rate. This rate will often be different ftom the flow rate measured at the beginning of the sampling period. That difference is usually due to the clogging of the filter, thereby adding increased resistance to the flow of air.

Once the pre-determined volume of air has been reached, the time was recorded as well as on the cassette. Before the pump was turned off, the cassette was angled upward and the cap replaced and the end plug. The cassettes were placed in sealed containers, labeled with an identifying code and a sample log was kept. The samples were then submitted to the laboratory to be analyzed for asbestos content. A chain of custody record was prepared and accompamed the samples to the laboratory.

43. Asbestos Analysis and Methodology

Each air sample is cross-referenced by field designation and lab internal code to ensure proper, consistent handling through a chain of custody. Sample preparation takes place within a HEPA Filter clean bench to avoid any possible contamination. Air sampling was conducted at a level approximating the breathing zone of persons anticipated to be present in the area during normal operations. Samples collected represent the typical airborne fiber concentration of the area.

5. Findings and Conclusions

Eight (8) initial background air samples were collected and analyzed via phase contrast microscopy (PCM) at building 100. Five (5) samples were analyzed via Transmission Electron Microscopy (TEM). After analysis via TEM. all were below the permissible limits.

CONFIDENTIAL, SUBJECT TO PROTECTIVE ORDER NO. 1, JAN. 2013 CITY_DEP_WORBY_CANNATA_SUBP_000000012

NYC-WTC_000409109

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000409109Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →