munw 3. A turnaround time of 24 hours is required for all samples.
Asbestos Air Monitoring
1. Five (5) ambient air samples shall be collected outside but in the general vicinity of the work site. Samplers shall be placed in reasonable proximity to the building and away from obstructions, vents, and drafts that may unduly affect airflow.
2. Five (5) air samples shall be collected per day during cleanup activities. The flow rate shall be set at the minimum collection flow rate specified by the manufacturer for the sampling pump. The flow rate shall not exceed 3 liters per minute. A minimum sampling volume of 3600 liters shall be collected.
Samples shall be collected at isolation barriers outside the work area, the clean room of the worker/waste decontamination facility, and outside of the building.
3. Sample collection methodologies shall be in accordance with Title 15, Chapter 1 of the Rules of the City of New York (RCNY) and AHERA regarding documentation and sample locations and the requirements set forth herein regarding the rates of flow, and required volumes to achieve the necessary analytical sensitivity.
4. Sampling equipment shall be placed at representative locations and away from obstruction. Sampling cassette must be placed on a tripod and not taped to existing surfaces. All air sampling equipment shall be pre- and post- calibrated to insure accurate air sampling volumes.
5. The Air Sampling Technician shall perform clearance air sampling after the areas are free of dust accumulations as determined by the Project Monitor. All surfaces must be completely dry prior to the start of sampling. Clearance air sampling shall be performed at each apartment. Five samples shall be collected in each apartment and two samples shall be collected at the first floor lobby. The elevator shaft shall be cleared separately. Clearance air monitoring shall be performed after the completion of all clean up activities at the work site. Clearance air sampling shall be aggressive and performed in accordance with Title 15, Chapter 1 of the RCNY Section 1-43 (a)-(d).
6. Clearance air samples shall be collected in accordance with the procedures specified in the NIOSH 7400 Method. The flow rate for collection of air samples shall be at least 10 liters per minute and no more than 15 liters per minute. Air sampling cassettes must be monitored to ensure the filters do not develop dark spots that would indicate clogging. The minimum sampling volume is 3600 liters. If clogging develops, the cassette must be changed.
7. All clearance air samples and completed chain of custody forms must be transported to the laboratory immediately after sampling is completed.
Clearance Criteria
1. The following clearance levels have been established by the USEPA for clean up activities resulting from the collapse of the WTC.
4 of 6
CITY_DEP_WORBY_CANNATA_SUBP_000030727
NYC-WTC_000407444
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000362690
Document detailing scope of asbestos-related air monitoring and site personnel requirements.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000362678
DEP scope of work for asbestos abatement and air monitoring at 114 Liberty Street.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000407433
Scope of work and monitoring plan for asbestos cleaning at 114 Liberty Street.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000429276
Draft chain-of-custody for 114 Liberty Street samples and lab analyses.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000424654
Draft scope of work for interior cleaning and air monitoring by licensed contractor at 114 Liberty Street.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000442883
Scope of work document for interior cleaning and asbestos monitoring at 114 Liberty Street.
13 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000443993
Draft scope of work for asbestos cleaning and air monitoring at 114 Liberty Street.
13 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000433356
Follow-up DEP scope of work for 114 Liberty Street asbestos/cleaning monitoring.
13 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000454690
Draft DEP scope of work for interior dust assessment and asbestos air monitoring at 114 Liberty Street.
13 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000425478
Draft scope of work document outlining environmental sampling, air monitoring, and cleaning procedures for the interior of 114 Liberty Street.
13 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000155443
Request to verify sampling methodologies and detection limits in the 114 Liberty Street monitoring specifications.
13 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000162815
Request for review of monitoring contractor specifications for air sampling, including sampling methodologies, limits of detection, and clearance criteria, with reference to prior…
13 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000362678
DEP scope of work for asbestos abatement and air monitoring at 114 Liberty Street.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000162815
Request for review of monitoring contractor specifications for air sampling, including sampling methodologies, limits of detection, and clearance criteria, with reference to prior…
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000162838
Correspondence regarding Schedule A forms and a draft scope of work for cleaning and air monitoring contracts at the site.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000362690
Document detailing scope of asbestos-related air monitoring and site personnel requirements.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000155407
Review of monitoring contractor specifications for asbestos and dioxin sampling at 114 Liberty Street.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000155443
Request to verify sampling methodologies and detection limits in the 114 Liberty Street monitoring specifications.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000362690
Document detailing scope of asbestos-related air monitoring and site personnel requirements.
Similar indexed content
NYC-WTC_000362678
DEP scope of work for asbestos abatement and air monitoring at 114 Liberty Street.
Similar indexed content
NYC-WTC_000407433
Scope of work and monitoring plan for asbestos cleaning at 114 Liberty Street.
Similar indexed content
NYC-WTC_000429276
Draft chain-of-custody for 114 Liberty Street samples and lab analyses.
Similar indexed content
NYC-WTC_000424654
Draft scope of work for interior cleaning and air monitoring by licensed contractor at 114 Liberty Street.
Similar indexed content