NYC-WTC_000373102
ATC indoor air quality measurements report for Stuyvesant High School dated June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗ATC IAQ report for Stuyvesant High School dated June 2002.
NYC-WTC_000407030–000407034OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan June 24, 2002 Indoor Air Quality Measurements Page 4 Stuyvesant High School (Md??) ATCPrpiectNpM5-19125-0246 In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PMt s concentration range for these rooms was 20 - 27 pg/m^ with an average of approximately 24 Tg/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
TVOCC^ncentradon
TVOCs inside the building were 0.0 ppm for all readings. The outdoor TVOC concentrations were also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following; • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • The barge operation at Pier 25 has been shut down.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were within applicable standards and guidelines. 2. Seventy-five (75) of the indoor temperature measurements were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). 3. One hundred and ten (110) of the indoor measurements for relative humidity were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. 5. One (1) of the indoor CO2 measurements was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level.
CITY_21MC1OO_OO3797828
NYC-WTC_000407033
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000373102
ATC indoor air quality measurements report for Stuyvesant High School dated June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406906
Indoor air quality measurements at Stuyvesant High School documented for NYC Board of Education, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406953
ATC IAQ report for Stuyvesant High School to NYC Board of Education, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335940
Indoor air quality measurements report for Stuyvesant HS, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335929
Indoor air quality measurements report for Stuyvesant HS, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335989
IAQ measurements collected June 20, 2002 at Stuyvesant High School for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406970
Indoor air quality measurements at Stuyvesant High School prepared for Board of Education, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000407013
ATC report of IAQ measurements conducted June 20, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373264
Letter/report detailing indoor air quality measurements at Stuyvesant High School on June 20, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274066
Report of IAQ measurements at Stuyvesant High School, May 31, 2002, for NYC Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000395300
ATC letter reporting indoor air quality assessment at Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229474
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000407058
IAQ measurements report for Stuyvesant High School; June 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335929
Indoor air quality measurements report for Stuyvesant HS, June 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373143
ATC indoor air quality report covering measurements at Stuyvesant High School, June 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373102
ATC indoor air quality measurements report for Stuyvesant High School dated June 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274066
Report of IAQ measurements at Stuyvesant High School, May 31, 2002, for NYC Board of Education.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335989
IAQ measurements collected June 20, 2002 at Stuyvesant High School for BOE.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000373102
ATC indoor air quality measurements report for Stuyvesant High School dated June 2002.
Similar indexed content
NYC-WTC_000406906
Indoor air quality measurements at Stuyvesant High School documented for NYC Board of Education, May 2002.
Similar indexed content
NYC-WTC_000406953
ATC IAQ report for Stuyvesant High School to NYC Board of Education, June 2002.
Similar indexed content
Indoor air quality measurements report for Stuyvesant HS, June 2002.
Similar indexed content
Indoor air quality measurements report for Stuyvesant HS, June 2002.
Similar indexed content