Mr. Bernard P. Orlan June 20, 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477)____________ ATC Project No. 15-19125-0246 Real-Time Environmental Measurements

ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 12:40 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 68.7 °F to 77.9 °F. Sixty-two (62) of the indoor measurements were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). The outdoor temperature was 68.7 to 77.9 °F.

Relative Humidity

The relative humidity indoors ranged from 52.6 percent to 65.9 percent. Sixty-five (65) of the indoor measurements for relative humidity were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity levels were 66.8 and 67.9 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 428 ppm to 1074 ppm. All of the CO2 measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 396 ppm and 400 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1100 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Cat±on^H)JwxideCpricentr^^

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 1 ppm for both readings.

Respirable Particulates (PM2_5)

Respirable particulate concentrations* indoors ranged between 25 pg/m^ to 33 pg/m^ with an average of approximately 28 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentrations were 45 and 48 pg/m3.

CITY_21MC1OO_OO37978O8

NYC-WTC_000407009

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000407009Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000395300

ATC letter reporting indoor air quality assessment at Stuyvesant High School, June 2002.

Similar indexed content

NYC-WTC_000213118

Cover letter and report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on June 14, 2002.

Similar indexed content

Compare copies and versions →