Indoor air quality report, Stuyvesant HS, June 2002

Machine-extracted title · confidence 42%

Report of IAQ measurements at Stuyvesant High School prepared for Board of Education, June 2002.

NYC-WTC_000406911–000406914
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan June 4, 2002 Indoor Air Quality Measurements Page 4 Stuvvesant High School (M477) ATCProiectNpM5J^125-0246 concentration range for these rooms was 7-18 pg/m^ with an average of approximately 11 Pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TYOCConcenlration

TVOCs inside the building were 0.0 ppm for all readings. The outdoor TVOC concentrations were also 0.0 ppm.

Oj^RVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • The barge operation at Pier 25 has been shut down.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO, CO2 and TVOCs were below applicable standards and guidelines. 2. Seventy-one (71) of the indoor measurements were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASIIRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). 3. All of the indoor measurements for relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. Six (6) of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or212.

Sincerely, .1TC ASSOCIA TES INC.

7

Yiannis EFstathiou Senior Project Manager

Attachment

CITY_21MC100_002903175

NYC-WTC_000406914

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000406914Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, February 2002

NYC-WTC_000197500

Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in February 2002.

Similar indexed content

NYC-WTC_000311555

ATC IAQ measurements report for Stuyvesant High School, Feb 2002.

Similar indexed content

NYC-WTC_000336237

IAQ measurements collected April 19, 2002 at Stuyvesant High School.

Similar indexed content

Compare copies and versions →