Mr. Bernard P. Orlan May 30 2002 Indoor Air Quality Measurements Page 4 Stuvvesant High School (’M477I ATC Proiect No. 15-19125-0246
In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2 5 concentration range for these rooms was 26 - 38 pg/m^ with an average of approximately 32 4g/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
TVOC Concentration
TVOCs inside the building were 0.0 ppm for all readings. The outdoor TVOC concentrations were also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • The barge operation at Pier 25 has been shut down.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. One-hundred and two (102) of the indoor measurements were below and sixteen (16) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). 3. One-hundred and eleven (111) of the indoor measurements for relative humidity were above and seven (7) of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. Twenty (20) of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. 5. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Two (2) of the one hundred and eighteen (118) instantaneous indoor readings were above the USEPA recommendation of 40 g/m3 for sensitive individuals and children.
CITY_21MC100_003797657
NYC-WTC_000406886
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000373161
Indoor air quality measurements collected at Stuyvesant High School, June 12, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000395300
ATC letter reporting indoor air quality assessment at Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406878
May 29, 2002 IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373022
ATC IAQ report for Stuyvesant High School dated May 31, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406861
May 28, 2002 IAQ report for Stuyvesant High School under ATC project 15-19125-0246.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406604
April 23, 2002 memo describing IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000407007
ATC IAQ report to NYC Board of Education for Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335929
Indoor air quality measurements report for Stuyvesant HS, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335940
Indoor air quality measurements report for Stuyvesant HS, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336148
May 2002 IAQ measurements at Stuyvesant High School for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406937
Indoor air quality measurements collected at Stuyvesant High School in June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373143
ATC indoor air quality report covering measurements at Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000395300
ATC letter reporting indoor air quality assessment at Stuyvesant High School, June 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336159
ATC IAQ measurements conducted May 29, 2002 at Stuyvesant High School for BOE review.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274066
Report of IAQ measurements at Stuyvesant High School, May 31, 2002, for NYC Board of Education.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406937
Indoor air quality measurements collected at Stuyvesant High School in June 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373022
ATC IAQ report for Stuyvesant High School dated May 31, 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373246
ATC indoor air quality measurements report for Stuyvesant High School, June 19, 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements collected at Stuyvesant High School, June 12, 2002.
Similar indexed content
ATC letter reporting indoor air quality assessment at Stuyvesant High School, June 2002.
Similar indexed content
NYC-WTC_000406878
May 29, 2002 IAQ measurements at Stuyvesant High School.
Similar indexed content
NYC-WTC_000373022
ATC IAQ report for Stuyvesant High School dated May 31, 2002.
Similar indexed content
NYC-WTC_000406861
May 28, 2002 IAQ report for Stuyvesant High School under ATC project 15-19125-0246.
Similar indexed content