NYC-WTC_000372830
Indoor air quality report for Stuyvesant High School dated May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Indoor air quality measurements at Stuyvesant High School, April 2002, by ATC Associates for DOE.
NYC-WTC_000406650–000406653OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 1,2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477)_______________ ATC ProiectNo. 15-19125-0246 Real-Time Environmental Measurements
ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 12:35 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 66.9°F to 73.6°F. One hundred and nine (109) of the measurements were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (summertime conditions). The outdoor temperature range was 49.9 to 57.8°F.
Relative Humidity
The relative humidity indoors ranged from 30.9 percent to 39.3 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort.. The outdoor relative humidity levels were 33.8 and 34.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 427 ppm to 1136 ppm. All of the CO2 measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 438 and 469 ppm. Therefore, the maximum acceptable level of CO, at this location was 1169 ppm (background level -1- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COj indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 2 ppm.
Respirable Particulates (PM2 i)
Respirable particulate concentrations* indoors ranged between 11 pg/m’ to 22 pg/m’ with an average of approximately 16 pg/m\ None of the indoor measurements were above the NPAAQS of 65 pg/m’ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommendation of 40 g/m’ for sensitive individuals and children. The outdoor respirable particulate concentrations were 30 and 43 pg/m’.
CITY_21MC100_002902900
NYC-WTC_000406652
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000372830
Indoor air quality report for Stuyvesant High School dated May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336289
ATC IAQ report for Stuyvesant High School; March 4, 2002 entry.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406712
IAQ measurements collected on May 9, 2002 at Stuyvesant High School for DOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406695
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406622
April 25, 2002 memo documenting IAQ measurements at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406666
Indoor air quality measurements at Stuyvesant High School, May 2002, for DOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229527
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on May 8, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336102
Indoor air quality measurements conducted May 14, 2002 at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000204475
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406733
IAQ measurements at Stuyvesant High School, May 2002, for DOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372796
Indoor air quality measurements collected May 1, 2002 at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406675
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000204475
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in April 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335912
Indoor air quality report for Stuyvesant High School, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336273
ATC IAQ report for Stuyvesant High School dated Apr 25, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336289
ATC IAQ report for Stuyvesant High School; March 4, 2002 entry.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336051
IAQ measurements collected April 30–May 2, 2002 for Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406622
April 25, 2002 memo documenting IAQ measurements at Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000372830
Indoor air quality report for Stuyvesant High School dated May 2002.
Similar indexed content
NYC-WTC_000336289
ATC IAQ report for Stuyvesant High School; March 4, 2002 entry.
Similar indexed content
NYC-WTC_000406712
IAQ measurements collected on May 9, 2002 at Stuyvesant High School for DOE.
Similar indexed content
NYC-WTC_000406695
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
Similar indexed content
NYC-WTC_000406622
April 25, 2002 memo documenting IAQ measurements at Stuyvesant High School.
Similar indexed content