Mr. Bernard P. Orlan April 22, 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477) ATC Protect No. 15-19125-0246 Real-Time Environmental Measurements

ATC collected one hundred and twenty- (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 12:20 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 69.8 °F to 77.8 °F. Thirty-one (31) of the measurements for indoor temperature were below and eighty-seven (87) measurements were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during summer conditions. The outdoor temperature range was 70.1 to 77.8°F.

Jtelative Humidity

The relative humidity indoors ranged from 52.7 percent to 63.9 percent. Thirty-five (35) measurements for relative humidity were above and eighty-three (83) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity levels were 55.2 and 57.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 445 ppm to 1186 ppm. All of the CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 463 and 536 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1236 ppm (background level -+■ 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 2 ppm.

Jiespirable Particulates (PM2_^)

Respirable particulate concentrations* indoors ranged between 20 pg/m^ to 47 pg/m^ with an average of approximately 30 pg/m3. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Seven (7) of the one hundred-eighteen (118) instantaneous readings were above the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentrations were 66 and 95 pg/m^.

CITY_21MC100_002902790

NYC-WTC_000406602

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000406602Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000336237

IAQ measurements collected April 19, 2002 at Stuyvesant High School.

Similar indexed content

Compare copies and versions →