Mr. Bernard P. Orlan April 15, 2002
Indoor Air Quality Measurements Page 3
Stuyvesant High School (M477)_______________ ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and twenty (120) sets of real-time environmental measurements
consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All
ten floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after
12:05 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 67.1 °F to 74.7°F. Three (3) of the
measurements were below the range of 68 to 75°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
The outdoor temperature range was 54.8 to 55.7°F.
Relative Humidity
The relative humidity indoors ranged from 30.1 percent to 43.8 percent. All measurements were
within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort.. The
outdoor relative humidity levels were 45.7 and 50.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 436 ppm to 1145 ppm. All of the CO2
measurements were within the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentrations were 425 and 441 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1141 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged
from Ippm to 2 ppm.
Respirable Particulates (PM2.5)
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 21 pg/m^ with an
average of approximately 15 pg/m^. None of the measurements were above the NPAAQS of 65
pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter or the USEPA recommendation of 40 pg/m^ for sensitive individuals and
children. The outdoor respirable particulate concentrations were 35 and 38 pg/m^.