NYC 9/11 Public Portal Document
600 West Cummings Park, Suite 6500
Woburn. Massachusetts 01801-6350
www.atcenviro.com
781.932.9400
Fax 781.932.6211
ASSOCIATES INC.
May 6, 2002
Mr. Bernard P. Orlan
New York City Board of Education
28-11 Queens Plaza North
Long Island City, NY 11101
Re; Dust Sampling for Asbestos & Lead
Stuyvesant High School (M477)/IS 306X
ATC Project No. 19125-0246
Dear Mr. Orlan:
As per your request, ATC Associates, Inc. conducted asbestos bulk sampling and lead
wipe sampling from settled dust in representative locations within the HVAC systems at
Stuyvesant High School and IS 306X. This testing was conducted on April 27, 2002 and
April 28, 2002. respectively. The purpose of this testing was to determine the asbestos and
lead content within settled dust present in representative locations within the HVAC
systems at both of these schools.
ATC performed a visual inspection within each of the units to be tested to determine if
visible dust was present prior to collecting each sample. Samples were collected at
locations where visible accumulations of dust were evident.
The analytical results of the testing conducted are as follows:
A. STUYVESANT HIGH SCHOOL
A total of fifteen (15) asbestos bulk samples were collected from various HVAC units
throughout the school. All samples were analyzed utilizing Polarized Light Microscopy
(PLM) methodology. No asbestos was detected in any of the fifteen (15) bulk samples
collected.
A total of fifteen (15) dust wipe samples were collected from various HVAC units
throughout the school. Laboratory analysis detected lead concentrations which ranged
between 253.0 pg/ft^ to less than the limit of detection of 9.0 pg/ft^.
CITY_21MC100_002902569
NYC-WTC_000406435
OCR can misread numbers and units. Confirm readings against the page image before using them.