NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, PS 89M, Feb 2002

Machine-extracted title · confidence 48%

Indoor air quality measurements collected at PS 89M for pre-occupancy.

NYC-WTC_000404395–000404398
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan February 18, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATCProiectNo. 15-19125-0297

Real-Time Environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of eight (8) outdoors and thirty-two (32) inside in the morning (A.M.) and the same number of readings in the afternoon (P.M.). All five floors of the school were surveyed. The field data sheets are found in the Attachment. Readings began at 8:00 A.M. and concluded after 3:30 P.M. The results are described below:

Temoerature

Indoor dry bulb temperature measurements ranged from 67.3^ to 71.5°F (A.M.) and 69.0°F to 72.9°F (PM). In the morning, one (1) of the measurements was below the range of 68 to 75‘’F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). In the afternoon, all measurements were within the recommended range. The average outdoor temperature was 41.5°F (A.M.) and 42.8°F (P.M.).

Relative Humidity

The relative humidity indoors ranged from 18.9 to 26.2 percent (A.M.) and 18.5 to 24.6 percent (P.M.). All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity averaged 35.9 percent (A.M.) and 24.2 percent (P.M.).

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 487 to 1021 ppm (A.M.) and 487 to 999 ppm (P.M.). All CO2 measurements collected were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations averaged 476 ppm (A.M.) and 465 ppm (P.M.). Therefore, the maximum acceptable level of CO2 at this location was 1176 ppm (background level + 700 ppm). The highest indoOr level was measured in Classroom 402. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. The 2^“^ and floors of the school building were not occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide was not detected indoors (0 ppm). The outdoor CO concentration was also 0 ppm (A.M.) and 0 ppm (P.M.).

Respirable Particulates (PM2 5)

Respirable particulate concentrations* indoors ranged from 10 pg/m3 to 16 pg/m3 (A.M.) and 10 gg/m^ to 18 gg/m^ (P.M.). All indoor measurements were below the NPAAQS of 65 gg/m^ (24-hour average). The average PM2.5 concentration* for the entire school building was approximately 11 gg/m^ (A.M.) and 15 gg/ra^ (P.M.). None of the indoor measurements were above the USEPA recommended concentration of 40 gg/m^ for sensitive individuals such as

CITY_21MC100_000491625 NYC-WTC_000404397

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000404397Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →