NYC 9/11 Public Portal Document
Paes Analytical Services, Inc.
1700 Elm Street, Suite 200
mAnalyticar Minneapolis, MN 55414
Phone: 612.607.1700
mfw.pacelabs.com REPORT ©F: CHEMICAL ANALYSES Fax: 612.607.6444
PROJECT: PCDD/PCDF ANALYSES DATE: April 5, 2002
PAGE: 7 REPORT NO: 02-1055017
RESULTS
The results from the analyses are presented in the following:
Appendix A - Documentation
Appendix B - PCDD/PCDF Analysis Results
DBSCUSSION
The recoveries of the isotopically-labeled PCDD/PCDF internal standards in the sample extracts
ranged from 64-117%. All of the internal standard recoveries for field samples were within the
. target limits for this method. Also, since the quantifications of the native 2,3,7,8-substituted
isomers were based on isotope dilution, the data were automatically corrected for variation in
recovery and accurate values were obtained.
A laboratory method blank was prepared and analyzed with the sample batch as part of our routine
quality control procedures. The results, found at the beginning of Appendix B, show the blank to be
free of PCDDs and PCDFs at the reporting limits. This indicates that the sample processing
procedures did not significantly impact the results of the analyses.
A laboratory spike sample was also prepared with the sample batch by extracting clean wipes that
had been fortified with native standard materials. The results, found at the end of Appendix B,
show that the spiked native compounds were recovered at 68-121%. These results indicate a
generally high degree of accuracy for these samples. It should be noted that one isomer in the
.. spike was recovered slightly below the target range for this method. The affected point is flagged
"P" on the data summary sheet.
REPORT OF LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, Inc.
/nelKA
CITY_21MC100_002898117
NYC-WTC_000402647
OCR can misread numbers and units. Confirm readings against the page image before using them.