Mr. Bernard P. Orlan March 22, 2002 Indoor Air Quality Assessment Page 4 H.S. of Economics and Finance (M833 ) ATC Project No. 15-19125-0291 Eleven (11) of the twelve (12) outdoor instantaneous readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
Tf^OC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following: o The interior of the building appeared clean and free of dust and debris; o The building was occupied at the time of the assessment; o No smoke odor was detected in the building;
FUNDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of respirable particulates, CO and TVOCs were below applicable standards and guidelines. 2. Fourteen (14) of the indoor measurements for temperature were below and seventy-four (74) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. Forty-eight (48) of the indoor measurements for relative humidity are below and forty (40) were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 4. Three (3) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading (1442 ppm) was measured in the cafeteria at approximately at 1:29 PM with 160 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. 5. All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. One (1) of the eighty-eight (88) instantaneous indoor readings was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. Seven (7) of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Eleven (11) of the twelve (12) outdoor instantaneous readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.
CITY_21MC100_002924294
NYC-WTC_000402536
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000384241
IAQ measurements collected at HS Economics & Finance per BOE request; March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402524
Indoor air quality measurements collected March 19, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219378
ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 8, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404462
IAQ measurements at HS of Economics and Finance, April 8, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402480
Indoor air quality measurements collected on March 14, 2002 for the specified school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384236
Indoor air quality measurements collected at HS Economics & Finance for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384192
IAQ measurements collected March 14, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384177
IAQ measurements collected March 13, 2002 at High School of Economics and Finance.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179980
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402465
Indoor air quality measurements collected at the referenced school in March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402495
Indoor air quality measurements collected on March 15, 2002 for the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384207
Indoor air quality measurements at HS of Economics & Finance for BOE, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000384241
IAQ measurements collected at HS Economics & Finance per BOE request; March 2002.
Similar indexed content
Indoor air quality measurements collected March 19, 2002 at the referenced school.
Similar indexed content
ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 8, 2002.
Similar indexed content
IAQ measurements at HS of Economics and Finance, April 8, 2002.
Similar indexed content
Indoor air quality measurements collected on March 14, 2002 for the specified school.
Similar indexed content