Mr. Bernard P. Orlan March 7, 2002 Indoor Air Quality Assessment Page 4 H.S. of Economics and Finance fMSBSl ATC Project No. 15-19125-0291 * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: o The interior of the building appeared clean and free of dust and debris; 0 The building was occupied at the time of the assessment; 0 No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

L Concentrations of CO, and TVOCs were below applicable standards and guidelines. 2. Fifty-two (52) indoor measurements for relative humidity were below and thirty-six (36) were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 3. Twenty-five (25) indoor temperature measurements were below and nineteen (19) were above the range of 68 to 75°F (at 50 percent relative humidity recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 4. Four (4) of the indoor measurements for carbon dioxide were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading was measured in stairwell A 8^^ floor at 1:09 PM. S. Two readings indicate Respirable Particulate concentration of 46 pg/m^ and 48 pg/m3 in locations Stairwell B 9th floor and Stairwell B 7th floor respectively.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 336 or 212.

Sincerely, A TCASSOCIA TES INC. Reviewed by:

Prasad Doddapanenl James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_002924140

NYC-WTC_000402412

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000402412Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000396488

Indoor air quality measurements collected May 9, 2002 for BOE.

Similar indexed content

NYC-WTC_000384111

IAQ report for High School of Economics and Finance, March 2002, coordinated by ATC.

Similar indexed content

Compare copies and versions →