IAQ report for High School of Economics and Finance based on measurements collected Mar 4, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Indoor air quality IAQ report for High School of Economics and Finance, measurements on Mar 1, 2002.
NYC-WTC_000402387–000402390OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 4, 2002 Indoor Air Quality Assessment Page 2 U.S. of Economics and Finance CMSBS) ATCPrpiectNpJ5-19125-0291
The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
parameter TARGET LEVEL AGENCY OR ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2,5) of air (pg/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_002924089
NYC-WTC_000402388
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000402391
IAQ report for High School of Economics and Finance based on measurements collected Mar 4, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259002
ATC report of IAQ measurements at High School of Economics and Finance (Feb 2002).
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383111
IAQ measurements collected April 18, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404489
IAQ measurements conducted at the referenced school as part of BOE program (Apr 16, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402395
IAQ measurements at the referenced school as part of BOE program, collected Mar 5, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179968
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 1, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383143
IAQ measurements collected April 23, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384246
Indoor air quality measurements collected on March 22, 2002 at HS Economics & Finance.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404504
IAQ measurements at the referenced school; BOE program participation (Apr 17, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259010
IAQ measurements conducted March 5, 2002 at H.S. of Economics and Finance (M833).
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383107
Indoor air measurements collected April 17, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259006
IAQ measurements at H.S. of Economics and Finance; scope of work (Mar 2002).
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000383076
ATC reports IAQ measurements taken April 10, 2002 at High School of Economics and Finance.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402391
IAQ report for High School of Economics and Finance based on measurements collected Mar 4, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397655
ATC IAQ measurements at PS 234M for indoor air quality assessment.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396707
ATC IAQ measurements collected June 13, 2002 under BOE directive for IAQ maintenance.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000222470
ATC Associates letter submitting indoor air quality measurement results collected on April 15, 2002, at P.S. 89M for the NYC Board of Education.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315412
ATC IAQ measurements report for P.S. 234M to Board of Education.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000402391
IAQ report for High School of Economics and Finance based on measurements collected Mar 4, 2002.
Similar indexed content
NYC-WTC_000259002
ATC report of IAQ measurements at High School of Economics and Finance (Feb 2002).
Similar indexed content
NYC-WTC_000383111
IAQ measurements collected April 18, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000404489
IAQ measurements conducted at the referenced school as part of BOE program (Apr 16, 2002).
Similar indexed content
NYC-WTC_000402395
IAQ measurements at the referenced school as part of BOE program, collected Mar 5, 2002.
Similar indexed content