Mr. Bernard P. Orlan March 18, 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477) ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded aifter 12:40 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 67.4‘’F to 75.7°F. Two (2) of the measurements were below and one (1) was above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 56.4 to 61.3 °F.
Relative Humidity
The relative humidity indoors ranged from 33.1 percent to 47.8 percent. All measurements were ! within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort.. The outdoor relative humidity levels were 41.4 and 47.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 476 ppm to 1126 ppm. All of the CO2 measurements were within the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 478 and 512 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1212 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air.' The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2 ppm to 3 ppm.
Respirable Particulates (PM2j)
Respirable particulate concentrations* indoors ranged between 15 pg/m^ to 46 pg/m^ with an average of approximately 22 pg/m3. None of the indoors measurements were above the NPAAQS of 65 pg/m^ One (1) of the indoors measurements was above the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentrations were 101 and 104 pg/m^.
CITY_21MC100_002923740
NYC-WTC_000402208
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000270018
ATC IAQ measurements conducted March 13, 2002 at Stuyvesant High School for NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402177
March 11, 2002 IAQ measurements report for Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000270030
ATC IAQ measurements conducted March 18, 2002 at Stuyvesant High School for NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402202
ATC IAQ report for Stuyvesant High School measurements, March 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229470
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 16, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336433
Indoor air quality measurements collected for Stuyvesant High School by ATC.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372779
Indoor air quality measurements collected at Stuyvesant High School, April 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406666
Indoor air quality measurements at Stuyvesant High School, May 2002, for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311665
Report of IAQ measurements collected on February 26, 2002 at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336060
IAQ measurements collected May 2, 2002 for Stuyvesant High School; BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336056
IAQ measurements collected May 1, 2002 for Stuyvesant High School; BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406560
April 15, 2002 memo referencing IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000336454
Indoor air quality measurements at Stuyvesant HS; March 18, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402202
ATC IAQ report for Stuyvesant High School measurements, March 14, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336411
ATC IAQ report for Stuyvesant HS; measurements collected March 11, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000270030
ATC IAQ measurements conducted March 18, 2002 at Stuyvesant High School for NYC BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000270022
ATC IAQ measurements conducted March 14, 2002 at Stuyvesant High School for NYC BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402099
ATC IAQ measurements conducted on Feb 28, 2002 for Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000270018
ATC IAQ measurements conducted March 13, 2002 at Stuyvesant High School for NYC BOE.
Similar indexed content
March 11, 2002 IAQ measurements report for Stuyvesant High School.
Similar indexed content
NYC-WTC_000270030
ATC IAQ measurements conducted March 18, 2002 at Stuyvesant High School for NYC BOE.
Similar indexed content
NYC-WTC_000402202
ATC IAQ report for Stuyvesant High School measurements, March 14, 2002.
Similar indexed content
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 16, 2002.
Similar indexed content