ATC IAQ measurements report for Stuyvesant High School, March 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗ATC IAQ report for Stuyvesant High School measurements, March 14, 2002.
NYC-WTC_000402202–000402205OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 15, 2002 Indoor Air Quality Measurements Page 4 Stuyvesant High School fM477) AHCPrpiectNpM5-19125-0246
In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 10-20 pg/m^ with an average of approximately 17 pg/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
TVOC Concentration TVOCs inside the building were 0.0 ppm to 0.1 ppm The outdoor TVOC concentrations were 0.0 ppm to 0.2 ppm.
OBSERVATIONS
During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • - • No smoke odor was detected in the building; FINDINGS
Based on the real-time measurements, the following findings are presented;
1. Concentrations of CO ,CO2, and TVOCs, were within applicable standards and guidelines. 2. Nine (9) measurements of relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 3. Three (3) temperature measurements were below and one (1) was above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 4. None of the indoor particulate measurements were above the NPAAQS of 65pg/m3 or above the USEPA recommendation of 40pg/m3 for sensitive individuals,and children. Both outdoor readings were above the USEPA recommendation of 40pg/m3 for sensitive individuals and children. It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212. Sincerely, ATC ASSOCIAT£S INC. Reviewed by:
Yiannis Efstathiou James R. Colm, CIH, Project Manager Regional Manager Industrial Hygiene Division
Attachment
J
CITY_21MC100_002923723
NYC-WTC_000402205
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000402206
ATC IAQ measurements report for Stuyvesant High School, March 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402156
ATC IAQ measurements report for Stuyvesant High School dated March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000270018
ATC IAQ measurements conducted March 13, 2002 at Stuyvesant High School for NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336433
Indoor air quality measurements collected for Stuyvesant High School by ATC.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406695
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000270030
ATC IAQ measurements conducted March 18, 2002 at Stuyvesant High School for NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402065
February 2002 ATC report on indoor air quality measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000270022
ATC IAQ measurements conducted March 14, 2002 at Stuyvesant High School for NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229527
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on May 8, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402177
March 11, 2002 IAQ measurements report for Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336458
Indoor air quality measurements collected March 18, 2002 at Stuyvesant HS.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406675
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000402206
ATC IAQ measurements report for Stuyvesant High School, March 15, 2002.
Similar indexed content
ATC IAQ measurements report for Stuyvesant High School dated March 2002.
Similar indexed content
NYC-WTC_000270018
ATC IAQ measurements conducted March 13, 2002 at Stuyvesant High School for NYC BOE.
Similar indexed content
Indoor air quality measurements collected for Stuyvesant High School by ATC.
Similar indexed content
NYC-WTC_000406695
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
Similar indexed content