IAQ data report, Stuyvesant High School, Mar 2002

Machine-extracted title · confidence 60%

March 12, 2002 IAQ measurements report for Stuyvesant High School.

NYC-WTC_000402182–000402185
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 13, 2002 Indoor Air Quality Measurements Page 3 Stuwesant Hieh School CM477') ATC Project No. 15-19125-0246

Real-Time Environmental Measurements

ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 12;10P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 68.2°F to 72.8°F. All of . the measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 49.6 to 52.9 °F.

Relative Humidity

The relative humidity indoors ranged from 24.7 percent to 37.1 percent. Sixty-five(65) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort.. The outdoor relative humidity levels were 29.6 and 31.2 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 498 ppm to 1176 ppm. All of the CO2 measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 528 and 567 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1267 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 ppm.

Respirable Particulates (PM2.S)

Respirable particulate concentrations* indoors ranged between 6 pg/m3 to 24 pg/m^ with an average of approximately 15 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommendation of 40 g/m^ for sensitive individuals and children. The outdoor respirable particulate concentrations were 28 and 29 pg/m^.

CITY_21MC100_002923686

NYC-WTC_000402184

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000402184Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000402116

March 1, 2002 IAQ measurements report for Stuyvesant High School.

Similar indexed content

NYC-WTC_000336429

BoE IAQ measurements at Stuyvesant HS; March 12–13, 2002.

Similar indexed content

Compare copies and versions →