ATC IAQ report for Stuyvesant High School measurements, March 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗ATC IAQ measurements report for Stuyvesant High School dated March 2002.
NYC-WTC_000402156–000402159OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr-. Bernard P. Orlan March 8, 2002 Indoor Air Quality Measurements Page 2 Stuyvesant High School fM477') ATCProiectNo. 15-19125-0246 The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy.
The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLEI TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CQ2)_________ ____ above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO)' USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 p,g/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter; 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AlHA = American Industrial Hygiene Association
CITY_21MC100_002923631
NYC-WTC_000402157
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000402202
ATC IAQ report for Stuyvesant High School measurements, March 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406626
April 26, 2002 memo referencing IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402161
March 8, 2002 IAQ measurements report for Stuyvesant High School.
15 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000269995
March 8, 2002 memo regarding IAQ sampling at Stuyvesant High School (M477).
15 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000204459
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336077
May 2002 indoor air quality measurements at Stuyvesant High School, per BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336438
Indoor air quality measurements documented for Stuyvesant HS.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336294
ATC IAQ measurements collected at Stuyvesant High School on Apr 29, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406695
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336065
IAQ measurements collected May 3, 2002 for Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372903
ATC collects IAQ measurements at Stuyvesant High School (M477) for May 9, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402065
February 2002 ATC report on indoor air quality measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000336438
Indoor air quality measurements documented for Stuyvesant HS.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000204528
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in March 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402238
ATC indoor air quality measurements at Stuyvesant High School, March 26, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000270058
ATC IAQ measurements collected March 25, 2002 at Stuyvesant High School for NYC BOE.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000270062
ATC IAQ measurements collected March 26, 2002 at Stuyvesant High School for NYC BOE.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406932
IAQ measurements at Stuyvesant High School for NYC Board of Education, June 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000402202
ATC IAQ report for Stuyvesant High School measurements, March 14, 2002.
Similar indexed content
NYC-WTC_000406626
April 26, 2002 memo referencing IAQ measurements at Stuyvesant High School.
Similar indexed content
NYC-WTC_000402161
March 8, 2002 IAQ measurements report for Stuyvesant High School.
Similar indexed content
March 8, 2002 memo regarding IAQ sampling at Stuyvesant High School (M477).
Similar indexed content
NYC-WTC_000204459
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in May 2002.
Similar indexed content