NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, Stuyvesant High School, Mar 2002

Machine-extracted title · confidence 61%

ATC indoor air quality report for Stuyvesant High School dated March 2002.

NYC-WTC_000402122–000402125
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlaii March 6, 2002 Indoor Air Quality Measurements Page 4 Stuyvesant High School (M477) ATCProiectNo. 15-19125-0246 In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 4-11 pg/m^ with an average of approximately 9

* The measurements made during this assessment were instantaneous readings, the NPAAQS is- a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATG noted the following; • The interior of the buildiiig appeared clean and free of dust and debris; . • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; .

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Measurements of temperature and concentrations of respirable particulates, CO ,CO2, and TVOCs, were within applicable standards and guidelines. 2. All measurements of relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. '

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.

Sincerely, Reviewed by: A TC ASSOCIA TES INC.

Q/Yiannis Efstathiou James R. Cohn, CIH, CSP Project Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_002923597

NYC-WTC_000402125

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000402125Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000336458

Indoor air quality measurements collected March 18, 2002 at Stuyvesant HS.

Similar indexed content

NYC-WTC_000402065

February 2002 ATC report on indoor air quality measurements at Stuyvesant High School.

Similar indexed content

Compare copies and versions →