NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, Stuyvesant HS, Dec 17 2001

Machine-extracted title · confidence 41%

Indoor air quality measurements collected December 17, 2001 at Stuyvesant High School.

NYC-WTC_000401506–000401509
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average. •

TVOCConcentration

TVOCs were not detected anywhere inside the building (0:0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted.the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the bui Iding; • Windows were open in Rooms 738 and'936.

FINDINGS

Based on the real-time measurements, the following findings are presented;

1. Measurements of relative humidity and concentrations of CO and TVOCs were within applicable standards and guidelines.

2. Seven (7) CO? measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. Ninety-five (95) temperature measurements were above the range recommended by ASHRAE 55-1992.

4. Thirty-three (33) measurements of respirable particulates were above the NPAAQS of 65 f-Lg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 26101-212.

Sincerely, ATC ASSOCIATES INC. Reviewed by:

Andreas C. Andreou James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_002897377

NYC-WTC_000401509

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000401509Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000273995

December 2001 IAQ measurements at Stuyvesant High School with BOE contact.

Similar indexed content

NYC-WTC_000401450

Indoor air quality measurements conducted December 10, 2001 at Stuyvesant High School.

Similar indexed content

NYC-WTC_000255518

IAQ measurements reported for Stuyvesant High School; December 10, 2001.

Similar indexed content

NYC-WTC_000273973

Memorandum regarding indoor air quality measurements at Stuyvesant High School.

Similar indexed content

Compare copies and versions →