Mr. Bernard P. Orlan January 29, 2002 Indoor Air Quality Assessment Page 2 P. S. 89M ATC Project No. 15-19125-0297
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAjE 62-J999}, American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED PAlLkMETER I lARGEl LFALL I AGEMA OR
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - recommendation for children/sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75 °F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_000490621 NYC-WTC_000400633
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000245379
Indoor air quality measurements for BOE at P.S. 89M.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245442
ATC IAQ measurements report for a NYC school prior to re-occupancy, Feb 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382540
Indoor air quality measurements at P.S. 89M prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245428
ATC letter transmitting IAQ report and scope of work for P.S. 89M, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382554
Indoor air quality measurements at P.S. 89M, Feb 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000359637
ATC memo re: IAQ report for PS 89M, Warren Street.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373529
Indoor air quality report for P.S. 234M, January 22, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000327337
ATC indoor air quality measurements at a NYC school, to evaluate air quality before re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396299
ATC IAQ measurements at PS 234M, January 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394408
Report of IAQ measurements at P.S. 89M in April 2002, per BOE request.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000326045
Cover letter/report detailing IAQ measurements at a NYC school for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313356
March 19, 2002 IAQ report for PS 89M site visit.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000400647
Report of IAQ measurements at PS 89M for BOE; January 29, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000218573
ATC Associates report on indoor air quality measurements at P.S. 89M requested by the Board of Education prior to re-occupancy.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000185979
Report from ATC Associates detailing indoor air quality measurements collected at PS 89M for the Board of Education.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384040
ATC IAQ measurements report for PS 89M dated January 24, 2002 to NYC BOE.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404315
ATC IAQ measurements at PS 89M requested by NYC BOE; report with findings.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404359
Indoor air quality measurements at PS 89M for re-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000245379
Indoor air quality measurements for BOE at P.S. 89M.
Similar indexed content
NYC-WTC_000245442
ATC IAQ measurements report for a NYC school prior to re-occupancy, Feb 2002.
Similar indexed content
NYC-WTC_000382540
Indoor air quality measurements at P.S. 89M prior to re-occupancy.
Similar indexed content
NYC-WTC_000245428
ATC letter transmitting IAQ report and scope of work for P.S. 89M, 2002.
Similar indexed content
NYC-WTC_000382554
Indoor air quality measurements at P.S. 89M, Feb 2002.
Similar indexed content