Mr. Bernard P. Orlan June 19, 2002 Indoor Air Quality Assessment Page 2 P. S. 234M ATC Project No. 15-19125-0279
The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLEI TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED PARAMETER
Carbon Dioxide TARGET LEVEL
<700 parts per million (ppm) AGEN ORGA ASHRAE62 s (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m3) 24-hour average 40 pg/m^ 24-hour average USEPA - recommendation for children/sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_002920770
NYC-WTC_000397686
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000315423
ATC IAQ measurements report for P.S. 234M sent to BOE.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372173
SCOPE OF WORK for IAQ tests at PS 234M, June 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315412
ATC IAQ measurements report for P.S. 234M to Board of Education.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315456
ATC report of IAQ measurements at PS 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397615
IAQ measurements collected for BOE program evaluating indoor air quality.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397715
ATC report on IAQ measurements at PS 234M for BOE program.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315350
ATC IAQ report letter accompanying measurements for P.S. 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397705
ATC IAQ measurements report for PS 234M; scope of work noted.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372203
ATC report detailing IAQ measurements at PS 234M, June 21, 2002, for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397301
IAQ measurements collected April 17, 2002 at PS 234M for BOE evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397675
ATC IAQ measurements collected to review indoor air quality status at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372193
SCOPE OF WORK for indoor air quality testing at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000397705
ATC IAQ measurements report for PS 234M; scope of work noted.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315467
ATC IAQ measurements report for BOE at PS 234M.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315456
ATC report of IAQ measurements at PS 234M for BOE.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372173
SCOPE OF WORK for IAQ tests at PS 234M, June 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397369
Indoor air quality measurements collected on Apr 29, 2002 at PS 234M.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314964
Indoor air quality measurements collected at P.S. 234M for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000315423
ATC IAQ measurements report for P.S. 234M sent to BOE.
Similar indexed content
NYC-WTC_000372173
SCOPE OF WORK for IAQ tests at PS 234M, June 2002.
Similar indexed content
NYC-WTC_000315412
ATC IAQ measurements report for P.S. 234M to Board of Education.
Similar indexed content
NYC-WTC_000315456
ATC report of IAQ measurements at PS 234M for BOE.
Similar indexed content
NYC-WTC_000397615
IAQ measurements collected for BOE program evaluating indoor air quality.
Similar indexed content