NYC-WTC_000315383
ATC IAQ measurements report for P.S. 234M sent to Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗ATC measurements to determine if acceptable IAQ is maintained at PS 234M.
NYC-WTC_000397645–000397648OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan June 13,2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279
Real-Time Environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty (50) from inside the school building and ten (10) outdoors. All three floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 11:06 AM and concluded after 1:00 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 71.7 °F to 81.4 °F. Four (4) of the indoor measurements for temperature were below and two (2) were above the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAF Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 84.8 °F to 84.9 °F.
Relative Humidity
The relative humidity indoors ranged from 48.4 percent to 61.3 percent. Seven (7) of the indoor measurements for relative humidity were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 52.1 percent to 52.6 percent.
Qn^bonDipxideConcentration
Carbon dioxide concentrations indoors ranged from 526 ppm to 1261 ppm. All of the indoor measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 603 ppm. Therefore, the maximum acceptable level of COg at this location was 1303 ppm (background level -t- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COg indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 1 ppm for all readings.
Respirable Particulates (PM2j)
Respirable particulate concentrations* indoors ranged between 15 pg/m^ to 52 pg/m^ with an average approximately 28 pg/m^- None of the measurements collected indoors for respirable particulate concentrations were above the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Eight (8) of the indoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 98 pg/m^ to 110 pg/m^ with an average of approximately 104 pg/m^.
CITY_21MC100_002920727
NYC-WTC_000397647
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000315383
ATC IAQ measurements report for P.S. 234M sent to Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223920
Cover letter from ATC Associates submitting indoor air quality measurement results for PS 234M collected on May 9, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315372
ATC IAQ measurements report for P.S. 234M prepared for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223944
Cover letter from ATC Associates submitting indoor air quality measurement results for PS 234M collected on May 24, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397655
ATC IAQ measurements at PS 234M for indoor air quality assessment.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199225
ATC Associates reports indoor air quality measurements collected at P.S. 234M on June 13, 2002 for the NYC Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372119
ATC IAQ measurements at PS 234M for BOE, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397439
ATC IAQ measurements at P.S. 234M per BOE directive, May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397635
ATC IAQ measurements at PS 234M to evaluate indoor air conditions.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315149
ATC IAQ measurements at PS 234M for BOE program, May 9, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199213
ATC Associates reports indoor air quality measurements collected at P.S. 234M on May 24, 2002 for the NYC Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397519
ATC IAQ measurements at PS234M on May 22, 2002 per BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000315383
ATC IAQ measurements report for P.S. 234M sent to Board of Education.
Similar indexed content
NYC-WTC_000223920
Cover letter from ATC Associates submitting indoor air quality measurement results for PS 234M collected on May 9, 2002.
Similar indexed content
NYC-WTC_000315372
ATC IAQ measurements report for P.S. 234M prepared for BOE.
Similar indexed content
NYC-WTC_000223944
Cover letter from ATC Associates submitting indoor air quality measurement results for PS 234M collected on May 24, 2002.
Similar indexed content
NYC-WTC_000397655
ATC IAQ measurements at PS 234M for indoor air quality assessment.
Similar indexed content