NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 31, 2002
Indoor Air Quality Assessment Page 4
P. S. 234M ATC Project No. 15-19125-0279
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO2, CO, and TVOCs were below applicable standards and guidelines.
2. Five (5) indoor measurements for temperature were below and none of the measurements
were above the range of 73 to 79°F (at 50 percent relative humidity) as recommended by
ASHRAE Standard 55-1992 during the summer season.
3. All of the indoor measurements for relative humidity were above the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort.
4. None of the measurements collected indoors for respirable particulate concentrations were
above the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5
micrometers or less in aerodynamic diameter and the USEPA recommended concentration of
40 pg/m^ for sensitive individuals and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or212.
Sincerely,
A TC ASSOCIA TES INC.
Reviewed by:
James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager, Industrial Hygiene Division
Attachment
CITY_21MC100_002920629
NYC-WTC_000397564
OCR can misread numbers and units. Confirm readings against the page image before using them.