Mr, Bernard P. Orlan June 27,2002
Indoor Air Quality Assessment Page 4
H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Indoor concentrations of CO and TVOCs were within applicable standards and guidelines.
2. Thirty-two (32) of the indoor measurements for temperature were above the range of 73 °F
to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992
during the summer season.
3. Ten (10) of the indoor measurements for relative humidity were above ASHRAE
recommended range of 30 to 60 percent for occupant comfort.
4. Eighteen (18) of the indoor measurements for respirable particulates were above the
NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers
or less in aerodynamic diameter. Thirty-two (32) of the indoor measurements were above
the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.
5, One (1) indoor CO2 measurement was above above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, ext. 211 or
212.
Sincerely,
A TC ASSOCIA TES INC.
Senior Project Manager
Attachment