Mr. Bernard P. Orlan June 10, 2002 Indoor Air Quality Assessment Page 2 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291 The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time date collected, ATC uses the commonly accepted guidelines cited in the following publications;
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refngerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 65-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists terget guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
Carbon Dioxide a® <700 parts per million (ppm) ASHRAE62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted fi-om (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperatxire Summer; 73-79°F at 50% RH ASHRAE 55 Winter; 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_002891722
NYC-WTC_000396692
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000396695
ATC IAQ measurements conducted June 10, 2002 for BOE program to maintain acceptable IAQ.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396687
ATC reports IAQ measurements at High School of Economics and Finance, June 2002, per BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385095
ATC IAQ measurements conducted June 11, 2002 for BOE at the High School of Economics and Finance.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385087
ATC IAQ measurements collected June 7, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396699
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384943
Indoor air quality report for measurements at the school, May 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396488
Indoor air quality measurements collected May 9, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223588
Report of indoor air quality measurements collected at the High School of Economics and Finance on May 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396683
IAQ measurements collected Jun 5, 2002 for school IAQ maintenance check.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384900
May 9-10 IAQ measurements at the school, part of BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259401
ATC indoor air quality measurements collected May 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396575
ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000396450
Indoor air measurements conducted May 6, 2002 for BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384192
IAQ measurements collected March 14, 2002 at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219870
Cover letter and summary report detailing indoor air quality measurements conducted at the High School of Economics and Finance.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396683
IAQ measurements collected Jun 5, 2002 for school IAQ maintenance check.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384125
Indoor air quality report for school, measurements and professional signatures.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396723
ATC IAQ measurements collected June 19, 2002 under BOE IAQ program.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC IAQ measurements conducted June 10, 2002 for BOE program to maintain acceptable IAQ.
Similar indexed content
ATC reports IAQ measurements at High School of Economics and Finance, June 2002, per BOE request.
Similar indexed content
ATC IAQ measurements conducted June 11, 2002 for BOE at the High School of Economics and Finance.
Similar indexed content
NYC-WTC_000385087
ATC IAQ measurements collected June 7, 2002 at the school.
Similar indexed content
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
Similar indexed content