NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 2,2002
Indoor Air Quality Assessment Page 4
H.S. of Economics and Finance (MSB 3) ATC Project No. 15-19125-0291
instantaneous measurements were above the USEPA recommended concentration of 40 pg/m^
for sensitive individuals and children.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
findings
Based on the real-time measurements, the following findings are presented:
1. Indoor concentrations of CO and TVOCs were below applicable standards and guidelines.
2. Twenty (20) measurements were below and sixty-eight (68) measurements were within the
range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard
55-1992 during the summer season.
3. Forty-two (42) of the indoor measurements for relative humidity were below and forty-six
(46) measurement were within the ASHRAE recommended range of 30 to 60 percent for
occupant comfort.
4. Twenty (20) of the indoor measurements for CO2 were above the ASHRAE Standard 62-
1999 recommended maximum concentration of <700 ppm above the background level. The
highest reading (3045 ppm) was measured in Room #608 around 10:38 AM with 31
occupants. Levels above the recommended maximum do not indicate a health risk. Carbon
dioxide measurements are used as an indicator of available outdoor air. The primary source
of CO2 indoors is occupant respiration.
5. All of the indoor measurements for respirable particulates were below the NPAAQS of 65
pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter. Three (3) of the eighty-eight (88) indoor instantaneous
measurements were above the USEPA recommended concentration of 40 pg/m^ for
sensitive individuals and children. Three (3) of the outdoor measurements for respirable
particulates were above the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. Nine (9) the twelve (12)
outdoor instantaneous measurements were above the USEPA recommended concentration
of 40 pg/m^ for sensitive individuals and children.
CITY_21MC100_002891309
NYC-WTC_000396414
OCR can misread numbers and units. Confirm readings against the page image before using them.