Indoor air quality memo, BOE school, 90 Trinity Place

Machine-extracted title · confidence 36%

April 2002 IAQ measurements at the referenced BOE school, with program context.

NYC-WTC_000394868–000394871
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 29, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service (M894'! ATC Project No. 15-19125-0290 * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. 70.0 °F to 19.1 °F. Fifty two (52) of the indoor measurements for temperature were below, two (2) measurements were above and seventy four (74) were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (summertime conditions). 3. The relative humidity indoors ranged from 18.3 percent to 43.4 percent. One hundred eighteen (118) of the indoor measurements for relative humidity were bellow and ten (10) measurements were within the ASHRAEfrecommended range of 30 to 60 percent for ■ occupant comfort. 4. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentration was 575 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1275 ppm (background level + 700 ppm).These two measurements were collected from Basement Gym Lounge (1631ppm), Basement Gym (1419ppm) with twenty five occupants. These measurements were collected at approximately 2:25 PM.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext. 290 or 212.

Sincerely, J TC ASSOCIA TES INC.

Prasad Doddapaneni James R. Cohn, CIH, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division

Attachment

CITY_21MC1OO_OO291877O

NYC-WTC_000394871

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000394871Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →