Mr. Bernard P. Orlan . April 24, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 diameter, and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour.average.

TYOC Concentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also .0 ' ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; ■

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO, and TVOCs were below applicable standards and guidelines. 2. One hundred thirty eight (138) of the indoor measurements for temperature were below, one (1) measurement was above, and twelve (12) measurements were within the range of 68 to 75°F (af50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. One (1) of the indoor measurements for relative humidity was bellow and one hundred and forty five measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and one (1) measurement was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children..

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext #211 or 212.

Sincerely, J TC ASSOCIA TES INC. Reviewed by:

J

Prasad Doddapaneni James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment

CITY_21MC100_002918712

NYC-WTC_000394816

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000394816Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000370492

Indoor air quality measurements collected March 12, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000394752

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

Compare copies and versions →