Mr. Bernard P. Orlan April 12, 2002 Indoor Air Quality Assessment Page 4 P. S. 89M ATC Project No. 15-19125-0297

respirable particulate concentration measurements ranged from 34 to 38 qg/m^ with an average of 36 pg/m^. All of the outdoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentrations

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The school building was occupied at the time of the assessment. • No smoke odor was detected in the building • The interior of the building appeared clean and free of dust and debris.

FINDINGS

Based on the real-time measurements, the following findings are presented;

1. Concentrations of CO2, CO and TVOCs were below the applicable standards and guidelines. 2. All of the indoor and outdoor measurements for PM2.5 were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. 3. Two (2) of the indoor measurements for temperature were below, fourteen (14) were above, and fifty-four (54) were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 4. Thirty-two (32) of the indoor measurements were below and thirty-eight (38) were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.

Sincerely, A Te~i4SSOCIA TES INC.

(A’ M Tmel Jav^l James R. Cohn, CIH, CSP Senior Pnoiect Manager Regional Manager, Industrial Hygiene Division

Attachment

CITY_21MC100_000490056 NYC-WTC_000394399

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000394399Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000199006

Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 7, 2002.

Similar indexed content

Compare copies and versions →