NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 10,2002
Indoor Air Quality Assessment Page 4
P. S. 89M ATC Project No. 15-19125-0297
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 2,4-hour average.
IVOC Concentration
rVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration wa.s also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The school building was occupied at the time of the assessment.
• No smoke odor was detected in the building
• The interior of the building appeared clean and free of dust and debris.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO, and TVOCs were below the applicable standards and guidelines.
2. All of the CO2 measurements were below the ASHRAE Standard 62-1999 recommended
maximum concentration of <700 ppm above the background level.
3. All of the indoor measurements of relative humidity were within the ASHRAE
recommended range of 30 to 60 percent for occupant comfort.
4. All temperature measurements were within the range of 68 to 75°F (at 50 percent relative
humidity’) as recommended by the ASHRAE Standard 55-1992 during the heating season
(wintertime conditions).
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or 212.
Sincerely,
.4 TC ASSOCIA TES INC.
Reviewed by: ---
/ /
I /Yiannis Efstathiou James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager
Industrial Hygiene Division
Attachment