NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor air quality report, High School of Economics, Jun 2002

Machine-extracted title · confidence 42%

ATC IAQ measurements conducted June 11, 2002 for BOE at the High School of Economics and Finance.

NYC-WTC_000385095–000385098
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan June 12, 2002 Indoor Air Quality Assessment Page 4 ITS^ofEeonomic^ndFinancefM^Y ATC Project No. 15-19125-0291 * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

Ti^OC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following; • The interior of the building appeared clean and free of dust and debns; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Indoor concentrations of CO and TVOCs were below applicable standards and guidelines. 2. Sixty-seven (67) of the indoor measurements for temperature were above the range of 73 °F to 79°F (at 50 percent relative humidity) recommended by ASHR/\E Standard 55-1992 during the summer season. 3. Ail the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 4. Thirteen (13) of the indoor measurements for CO2 were above the ASHRAE Standard 62- 1999 recommended maximum concentration of <700 ppm above the background level. S. Eight (8) of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and nine (9) of the indoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext 211 or 212,

Sincerely, Reviev^b^ ATCASSOC/A TES INC. ■'f f ^iannis Efsri James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment

CITY_21MC100_002882501

NYC-WTC_000385098

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000385098Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000396699

ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.

Similar indexed content

NYC-WTC_000396695

ATC IAQ measurements conducted June 10, 2002 for BOE program to maintain acceptable IAQ.

Similar indexed content

NYC-WTC_000396687

ATC reports IAQ measurements at High School of Economics and Finance, June 2002, per BOE request.

Similar indexed content

NYC-WTC_000396691

ATC IAQ measurements from June 7, 2002 at the referenced school for BOE monitoring.

Similar indexed content

Compare copies and versions →