NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ memo, School of Economics and Finance, June 2002

Machine-extracted title · confidence 40%

ATC IAQ measurements collected June 5, 2002 at the school.

NYC-WTC_000385079–000385082
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan June 6, 2002 Indoor Air Quality Assessment Page 4 H.S, of Economics and Finance (M833) ATC Project No, 15-19125-0291 * The ineasurenients made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Indoor concentrations of CO and TVOCs were below applicable standards and guidelines. 2. Eighty-six (86) of the indoor measurements for temperature were above and Eight (8) of the measurements were within the range of 73 °F to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. 3. All the indoor measurements for relative humidity bellow the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 4. Four (4) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 599 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1299 ppm (background level + 700 ppm). The highest concentration (1467 ppm) was recorded in the Kitchen at about 1:58 PM with 3 occupants.

5. None of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and five (5) of the measurements was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext 290

Sincerely, ATC ASSOCIATES INC.

Prasad Doddapaneni* Senior Project Manager

Attachment

CITY_21MC100_002882433

NYC-WTC_000385082

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000385082Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000396683

IAQ measurements collected Jun 5, 2002 for school IAQ maintenance check.

Similar indexed content

NYC-WTC_000396516

Indoor air quality measurements collected May 13, 2002 for BOE.

Similar indexed content

NYC-WTC_000396687

ATC reports IAQ measurements at High School of Economics and Finance, June 2002, per BOE request.

Similar indexed content

NYC-WTC_000396679

IAQ measurements collected Jun 4, 2002 for BOE monitoring.

Similar indexed content

NYC-WTC_000396488

Indoor air quality measurements collected May 9, 2002 for BOE.

Similar indexed content

Compare copies and versions →