Mr. Bernard P. Orlan January 24, 2002 Indoor Air Quality Assessment Page 2 P. S. 89 (Manhattan) ATC Project No. 15-19125-0297
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHHAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED PARAMEIER • AGENCY OR ORGANlZATIONSr* PS Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer; 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30-60% ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC1OO_OO3775336
NYC-WTC_000384034
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000245343
ATC Associates reports IAQ measurements conducted at the referenced school for the NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000226873
ATC Associates report on indoor air quality measurements collected at P.S. 89M on January 17, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400594
Report of indoor air quality measurements at PS 89M for BOE project.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383993
ATC IAQ measurements collected January 17–18, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249454
Indoor air quality measurements collected January 23, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397291
IAQ measurements at PS 234M; BOE requested assessment of air quality.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314815
IAQ measurements collected March 19, 2002 at PS 234M for BOE.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314989
INS IAQ measurements collected at P.S. 234M; BOE referenced.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314771
Indoor air quality measurements collected March 26, 2002 at PS 234M.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314985
Indoor air quality measurements collected at P.S. 234M.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392852
ATC IAQ report for May 14, 2002 measurements at PS 89M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397251
IAQ measurements report for P.S. 234M, Apr 2002; scope of work described.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000245343
ATC Associates reports IAQ measurements conducted at the referenced school for the NYC BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400563
IAQ report for January 18, 2002, at PS 89M with multiple measurements.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384011
ATC IAQ measurements collected January 21, 2002 at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400594
Report of indoor air quality measurements at PS 89M for BOE project.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400572
IAQ report for January 21, 2002 at P.S. 89M with measurement results.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245312
Indoor air quality measurements at P.S. 89M; January 19, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000245343
ATC Associates reports IAQ measurements conducted at the referenced school for the NYC BOE.
Similar indexed content
NYC-WTC_000226873
ATC Associates report on indoor air quality measurements collected at P.S. 89M on January 17, 2002.
Similar indexed content
NYC-WTC_000400594
Report of indoor air quality measurements at PS 89M for BOE project.
Similar indexed content
NYC-WTC_000383993
ATC IAQ measurements collected January 17–18, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000249454
Indoor air quality measurements collected January 23, 2002 at PS 234M.
Similar indexed content