Mr. Bernard P. Orlan January 19. 2002 Indoor Air Quality Assessment Page 3 P. S. 89 (Manhattan) ATC Project No. 15-19125-0297

Real-Time Environmental Measurements

ATC collected fifty (50) sets of real-time environmental measurements consisting of fourty'-eight (48) from inside the school building and two (2) outdoors from the playground. All five floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:10 A.M. and concluded after 12:35 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 67.5 °F to 75.1 °F. Si.\ (6) measurements were below and one (1) was above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements at tlie playground ranged from 41.9 to 42.7 °F.

Relative Humidity

The relative humidity indoors ranged from 15.4 percent to 24.3 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 22.6 to 22.9 percent.

Carlin Qioxide Concentration

Carbon dioxide concentrations indoors ranged from 409 ppm to 701 ppm. All CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 433 and 440 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1140 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 Indoors is occupant respiration. The school building during ATC’s assessment was not occupied.

Carbon Monoxide Concentration

Carbon rhonoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 18 gg/m^ to 32 gg/mY All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 24 pg/mYThe outdoor respirable particulate concentration ranged from 35-36 pg/m^.

CITY_21MC100_003775303

NYC-WTC_000384004

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000384004Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →