Mr. Bernard P. Orlan March 5. 2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279
RealJXme Environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifn- (50 ) from inside the school building and ten (10) outdoors. All three floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded after 2:00 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 61.4 °F to 74.6 °F. Four (4) indoor measurements were below and forty-six (46) are within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 37.6 to 39.3 °F.
Relative Humidity
The relative humidity indoors ranged from 13.2 percent to 21.7 percent. All of the indoor of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 13 to 14.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 540 ppm to 988 ppm. All of the indoor measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 469 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1169 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 0 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 19 pg^m^. All measurements were below the NPAAQS of 65 pgm- 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 11 pg/m^. This average concentration was below the USEPA recommended concentration for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentration ranged from 13 to 30 pg/m^ with an average of 17 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC100_002877621
NYC-WTC_000381335
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000294357
IAQ measurements at P.S. 234M and Greenwich St. school site, dated March 4, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314914
Indoor air quality measurements collected at P.S. 234M per BOE program.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315332
ATC letter accompanying IAQ measurements report for P.S. 234M, June 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000217747
ATC Associates letter reporting indoor air quality measurements collected at P.S. 234M on March 14, 2002, as requested by the NYC Board of Education.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397581
Measurement results from June 3, 2002, evaluating indoor air quality at P.S. 234M per BOE request.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199221
ATC Associates reports indoor air quality measurements collected at P.S. 234M on June 6, 2002 for the NYC Board of Education.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397611
ATC IAQ measurements collected to determine if acceptable indoor air quality is maintained.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315321
ATC IAQ measurements at PS 234M; BOE program, June 5, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372105
ATC reports IAQ measurements at PS 234M, June 2002, for BOE to assess indoor air quality.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397591
ATC IAQ measurements at PS 234M to determine maintenance of acceptable indoor air quality.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371885
ATC indoor air quality measurements at PS 234M, April 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315061
Indoor air quality measurements collected April 26, 2002 for PS 234M.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000217747
ATC Associates letter reporting indoor air quality measurements collected at P.S. 234M on March 14, 2002, as requested by the NYC Board of Education.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314914
Indoor air quality measurements collected at P.S. 234M per BOE program.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182899
Report of indoor air quality measurements collected at PS 234M on February 25, 2002, to determine if acceptable air quality is maintained.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382080
ATC Associates indoor air quality report for PS 234M dated February 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000381400
ATC IAQ field report for PS 234M, March 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382090
Report of indoor air quality measurements at a New York City school, requested by the Board of Education, Feb 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000294357
IAQ measurements at P.S. 234M and Greenwich St. school site, dated March 4, 2002.
Similar indexed content
NYC-WTC_000314914
Indoor air quality measurements collected at P.S. 234M per BOE program.
Similar indexed content
NYC-WTC_000315332
ATC letter accompanying IAQ measurements report for P.S. 234M, June 2002.
Similar indexed content
NYC-WTC_000217747
ATC Associates letter reporting indoor air quality measurements collected at P.S. 234M on March 14, 2002, as requested by the NYC Board of Education.
Similar indexed content
NYC-WTC_000397581
Measurement results from June 3, 2002, evaluating indoor air quality at P.S. 234M per BOE request.
Similar indexed content