Mr. Bernard P. Orlan February 5, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadershin & Pub. Service fM894') ATC Project No. 15-I9I25-Q290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and thirty-four (134) in the school building and six (6) outdoors. All fourteen floors of the school were sun'eyed in the morning (A.M.) and afternoon (P.M.). Field data sheets are found in the Attachment. Readings began at 8:30 A.M. and concluded after 3:00. P.M. The results are described below:
Temperature
Indoor dry bulb temperature measurements ranged from 68.0°F to 74.2°F (A.M.) and 67.6°F to 73.2°F (P.M.). All of the measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The average outdoor temperatures were 42.2°F (A.M.) and 49.8°F (P-M.).
Relative Humidity
The relative humidity indoors ranged from 21.5 percent to 45.9 percent (A.M.) and 21.1 percent to .41.7 percent (P.M.). All but three of the measurements were below the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. Two morning and one afternoon measurements, from the Basement and Level C, were above 40 percent. The average outdoor relative humidity levels were 23.5 percent (A.M.) and 22.0 percent (P.M.).
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 470 ppm to 1339 ppm (A.M.) and 514 ppm to 1214 ppm (P.M.). Four (4) of the measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The average outdoor (background) CO2 concentrations were 405 ppm (A.M.) and 445 ppm (P.M.). Therefore, the maximum acceptable level of CO2 at this location was 1145 ppm (background level + 700 ppm). The highest A.M. reading was recorded in Room B06, occupied by 36 people, which also had the highest temperature and relative humidity. The highest P.M. reading was in Room 805 which was occupied by 33 people. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors in the A.M. was 1-2 ppm. The P.M. level was 1 ppm for all but one reading (0 ppm was recorded in the Library). These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1-3 ppm..
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 28 pg/m^ (A.M.) and 6 pg/m3 to 35 pg/m^ (P.M.). None of the measurements were above the NPAAQS of 65 pg/m^
CITY_21MC100_002871636
NYC-WTC_000376900
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000188373
Memo reporting indoor air quality measurements collected at a school on May 13, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372233
IAQ measurements collected June 26, 2002 at PS 234M.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377024
Indoor air quality measurements for High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182875
Report of indoor air quality measurements collected at PS 234M on February 7, 2002, as part of a program to maintain acceptable air quality.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314726
Report of IAQ measurements at PS 234M for BOE; Feb 7, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274722
ATC IAQ measurements for PS 89M, March 6, 2002, requested by BOE.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274710
ATC report of IAQ measurements conducted March 5, 2002 at PS 89M for NYC BOE.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274646
Indoor air quality measurements collected Feb 14, 2002 for P.S. 89M.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400182
IAQ field report for PS 89M, March 11, 2002, ATC.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000272200
ATC indoor air quality report for P.S. 234M, Feb 8, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377084
Correspondence reporting indoor air quality measurements at a NYC school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369362
IAQ measurements report for PS 89M following BOE request
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000297659
Indoor air quality measurements report for High School for Leadership & [name], Feb 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274622
Indoor air quality evaluation report for P.S. 89M; measurements on Feb 12, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400632
Report of indoor air quality measurements at PS 89M; January 28, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382575
Indoor air quality measurements collected Feb 7, 2002 at P.S. 89M.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382619
Report of indoor air quality measurements at P.S. 89M requested before re-occupancy.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274646
Indoor air quality measurements collected Feb 14, 2002 for P.S. 89M.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000188373
Memo reporting indoor air quality measurements collected at a school on May 13, 2002.
Similar indexed content
NYC-WTC_000372233
IAQ measurements collected June 26, 2002 at PS 234M.
Similar indexed content
NYC-WTC_000377024
Indoor air quality measurements for High School for Leadership & [name].
Similar indexed content
NYC-WTC_000182875
Report of indoor air quality measurements collected at PS 234M on February 7, 2002, as part of a program to maintain acceptable air quality.
Similar indexed content
NYC-WTC_000314726
Report of IAQ measurements at PS 234M for BOE; Feb 7, 2002.
Similar indexed content