Mr. Bernard P. Orlan February 6, 2002 Indoor Air Quality Assessment Page 3 P^50M ATCProiectNoM5;T9125-02^
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of twenty- nine (29) from inside the school building and eleven (11) from the outdoors. All three floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 11:00 A.M. and concluded at approximately 3:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 70.0°F to 76.3°F. Two (2) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 32.1 to 37.1°F.
Relative Humidity
The relative humidity indoors ranged from 11.4 to 16.4 percent. All of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 7.5 to 13.9 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 614 ppm to 1180 ppm. All of the CO2 measurements was below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 519 ppm. Therefore, the maximum acceptable level of COn at this location was 1219 ppm (background level -L 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon ARmoxide Concentration
Carbon monoxide concentrations indoors were 0 ppms for the interior readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm for all collected readings.
Respirable Particulates (PM2,3)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 22 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 15 pg/m^. The PM2.5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration measurements ranged from 7 to 19 pg/m^ with an average of 12 pg/m^.
CITY_21MC100_002853449
NYC-WTC_000375467
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000300651
ATC indoor air quality evaluation at PS 150M for re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300642
ATC IAQ measurements for PS 150M prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300655
ATC IAQ field report for PS 150M, Feb 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289350
Indoor air quality measurements collected for PS 150M; BOE-ordered.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000194816
Cover letter for indoor air quality measurements collected at PS150M on February 15, 2002, submitted to the Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375501
ATC IAQ measurements at P.S. 150M before re-occupancy, March 25, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375513
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300714
ATC IAQ measurements at PS 150M in March 2002 for pre-occupancy evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000214968
Letter from ATC Associates reporting indoor air quality measurements collected at PS 150M on March 27, 2002, prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300811
IAQ measurements at PS 150M prior to re-occupancy, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375533
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375529
Indoor air quality measurements at P.S. 150M, March 6, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000300633
ATC IAQ report covering measurements at PS 150M for re-occupancy
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375541
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400137
ATC IAQ report for PS 89M, March 4, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394376
Indoor air quality measurements at PS 89M for BOE; April 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392600
ATC report detailing IAQ measurements conducted April 9, 2002 at P.S. 89M per BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289350
Indoor air quality measurements collected for PS 150M; BOE-ordered.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000300651
ATC indoor air quality evaluation at PS 150M for re-occupancy.
Similar indexed content
NYC-WTC_000300642
ATC IAQ measurements for PS 150M prior to re-occupancy.
Similar indexed content
NYC-WTC_000300655
ATC IAQ field report for PS 150M, Feb 2002.
Similar indexed content
NYC-WTC_000289350
Indoor air quality measurements collected for PS 150M; BOE-ordered.
Similar indexed content
NYC-WTC_000194816
Cover letter for indoor air quality measurements collected at PS150M on February 15, 2002, submitted to the Board of Education.
Similar indexed content