ATC IAQ measurements report for P.S. 150M,June 20, 2002, pre-occupancy assessment.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗ATC IAQ measurements at P.S. 150M, June 24, 2002, pre-occupancy assessment.
NYC-WTC_000374972–000374975OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan June 25, 2002 Indoor Air Quality Assessment Page 2 P. S. 150M ATC Protect No. 15-19125-0289 r The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-/999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED ER targituevel AGENCY OR ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (fig/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter; 68-75°F at 50% RH Relative Humidity 30-60% ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_002870818
NYC-WTC_000374973
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000374956
ATC IAQ measurements report for P.S. 150M,June 20, 2002, pre-occupancy assessment.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253855
ATC IAQ measurements at PS 150M for pre-occupancy review.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374964
ATC IAQ measurements at P.S. 150M prior to occupancy; June 21, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253831
Indoor air quality measurements at PS 150 for occupancy pre-reporting.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250060
ATC letter describing IAQ measurements conducted at the school for re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374928
ATC IAQ measurements at school prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374932
ATC IAQ measurements at school prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374912
IAQ measurements collected for school prior to occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253782
ATC IAQ measurements at PS150M prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253811
ATC IAQ measurements at PS 150M prior to re-occupancy; results documented.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178791
Cover letter from ATC Associates submitting indoor air quality measurements collected at P.S. 150M on June 18, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374940
ATC reports IAQ measurements at P.S. 150M, NYC BOE, June 18, 2002, prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000250060
ATC letter describing IAQ measurements conducted at the school for re-occupancy.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404395
Indoor air quality measurements collected at PS 89M for pre-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404383
Report of indoor air quality measurements at PS 89M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000218569
Letter reporting indoor air quality measurements collected at P.S. 89M on February 11, 2002, to evaluate conditions prior to re-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253827
ATC IAQ measurements at PS 150 prior to occupancy; data included.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384040
ATC IAQ measurements report for PS 89M dated January 24, 2002 to NYC BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000374956
ATC IAQ measurements report for P.S. 150M,June 20, 2002, pre-occupancy assessment.
Similar indexed content
NYC-WTC_000253855
ATC IAQ measurements at PS 150M for pre-occupancy review.
Similar indexed content
NYC-WTC_000374964
ATC IAQ measurements at P.S. 150M prior to occupancy; June 21, 2002.
Similar indexed content
NYC-WTC_000253831
Indoor air quality measurements at PS 150 for occupancy pre-reporting.
Similar indexed content
NYC-WTC_000250060
ATC letter describing IAQ measurements conducted at the school for re-occupancy.
Similar indexed content