Mr. Bernard P. Orlan May 21,2002 Indoor Air Quality Assessment Page 4 P.S. ISOM ATC Project No. 15-19125-0289 respirable particulate concentration measurements ranged from 18 to 26 pg/m^ with an average of 22 pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentrations

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following; • There was construction work going on in the plaza; • The school building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented;

1. Concentrations of respirable particulates, CO and TVOCs were within applicable standards and guidelines; 2. All temperature measurement were below the range of 73 to 79® F (at 50 percent relative humidity recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). 3. Twenty-nine (29) measurements of relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 4. One (1) CO2 measurement was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 21 lor 212.

Sincerely, Reviewed by: A TC ASSOCIA TES INC.

(yYiannis Efstathiou James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment

CITY_21MC100_002870604

NYC-WTC_000374811

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000374811Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →