ATC IAQ measurements at PS 150M for pre-occupancy BOE evaluation, May 3, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗ATC IAQ measurements at PS 150M; BOE re-occupancy evaluation, May 2, 2002.
NYC-WTC_000374732–000374735OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 3, 2002 Indoor Air Quality Assessment Page 2 P. S. 150M ATC Project No. 15-19125-0289
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
yentilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refiigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditionsfor Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2 5) of air (fxg/m3) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer; 73-79°F at 50% RH ASHRAE 55 Winter: 68-75®F at 50% RH Relative Humidity 30 - 60% ASHRAE55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AKA = American Industrial Hygiene Association
CITY_21MC100_002870494
NYC-WTC_000374733
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000374740
ATC IAQ measurements at PS 150M for pre-occupancy BOE evaluation, May 3, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253663
IAQ measurement summary for PS 150M school, May 2002, by ATC.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000214370
Letter transmitting indoor air quality measurement results collected at P.S. 150M on April 30, 2002, for pre-reoccupancy evaluation.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253655
IAQ measurement summary for PS 150M prior to re-occupancy, May 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374716
ATC IAQ report for PS 150M prior to re-occupancy, date not fully shown; includes scope.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253747
ATC IAQ measurements at PS 150M for pre-occupancy evaluation.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374700
ATC reports IAQ measurements taken April 24, 2002 at P.S. 150M for BOE air quality review.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300691
ATC IAQ measurements at PS 150M before re-occupancy, Feb 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374724
ATC IAQ measurements at PS 150M for school building re-occupancy assessment, May 1, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249820
Indoor air quality measurements for PS 150M, prior to occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253623
ATC IAQ measurements conducted for BOE pre-occupancy evaluation.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253831
Indoor air quality measurements at PS 150 for occupancy pre-reporting.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000374988
ATC IAQ measurements collected June 26, 2002 at P.S. 150M for pre-occupancy check.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374880
ATC IAQ measurements at the school prior to re-occupancy.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374840
IAQ measurements at PS 150M for BOE pre-occupancy review, May 24, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374748
ATC IAQ report for PS 150M; date range May 6-7, 2002; BOE pre-occupancy measurements.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374756
ATC IAQ report for PS 150M; scope of work begins May 7, 2002; BOE pre-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300651
ATC indoor air quality evaluation at PS 150M for re-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000374740
ATC IAQ measurements at PS 150M for pre-occupancy BOE evaluation, May 3, 2002.
Similar indexed content
NYC-WTC_000253663
IAQ measurement summary for PS 150M school, May 2002, by ATC.
Similar indexed content
NYC-WTC_000214370
Letter transmitting indoor air quality measurement results collected at P.S. 150M on April 30, 2002, for pre-reoccupancy evaluation.
Similar indexed content
NYC-WTC_000253655
IAQ measurement summary for PS 150M prior to re-occupancy, May 2002.
Similar indexed content
NYC-WTC_000374716
ATC IAQ report for PS 150M prior to re-occupancy, date not fully shown; includes scope.
Similar indexed content