Mr. Bernard P. Orlan January 24, 2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0297

Real-Time Environiviental Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-nine (59) from inside the school building and one (1) outdoor. All three floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 10:00 A.M. and concluded after 11:45 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 64.6 °F to 76.1 °F. Three (3) measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE-Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurement was 51.3 °F.

Relative Humidity

The relative humidity indoors ranged from 18.4 percent to 23.4 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity was 17.3 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 468 ppm to 639 ppm. All CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 480 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1180 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. The school building during ATC’s assessment was not occupied.

C^bpnMoiwxideCpncentroidpn

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.

Respirable Particulates (PM2,s)

Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 21 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter as well as the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The average

CITY_2IMCl0 0_0 0 0 4 6 2 2 4 3 NYC-WTC_000373527

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000373527Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →